Design · Concrete
Effective buckling length for unbraced column l0
Effective buckling length of an unbraced compression member in a sway frame to EN 1992-1-1 Eq. (5.16).
Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.
Formula and quantities
| Symbol | Name | Unit | Note |
|---|---|---|---|
| Clear height of compression member | m | ||
| Relative flexibility of rotational restraint at end 1 | 1 | ||
| Relative flexibility of rotational restraint at end 2 | 1 | ||
| Effective buckling length | m | Result |
Worked example
= 3.5 m · = 0.5 1 · = 0.5 1
= 6.5479 m · Source: EN 1992-1-1:2004 Eq. (5.16)
Scope and standard
Unbraced reinforced concrete frame columns to EN 1992-1-1.
- Standard
- EN 1992-1-1:2004, clause 5.8.3.2 (3), Eq. (5.16)
- Result
- in m
Reference to clause and equation, no standard text. The description is written in our own words.