Design fire load density qf,d (EN 1991-1-2)
Design fire load density per unit floor area according to EN 1991-1-2 Annex E Eq. (E.1): qfd = qfk · m · δq1 · δq2 · δn.
- EN 1991-1-2:2002
Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.
Formula and quantities
| Symbol | Name | Unit | Note |
|---|---|---|---|
| Characteristic fire load density (in MJ/m^2) | 1 | ||
| Combustion factor (typically 0.8) | 1 | ||
| Fire activation risk factor for compartment size | 1 | ||
| Fire activation risk factor for occupancy type | 1 | ||
| Combined active fire fighting measures factor | 1 | ||
| Design fire load density (in MJ/m^2) | 1 | Result |
Worked example
= 511 1 · = 0.8 1 · = 1.5 1 · = 1 1 · = 0.61 1
= 374.05 1
Standard and source
- Standard
- EN 1991-1-2:2002
- Result
- in 1
Reference to clause and equation, no standard text. The description is written in our own words.