EN 1991-1-2 附属書A 式(A.4)によるパラメトリック温度時間曲線用の火災区画開口係数 O: O = (Av · √(heq / m)) / At.
- EN 1991-1-2:2002
Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.
Formula and quantities
| Symbol | Name | Unit | Note |
|---|---|---|---|
| 全壁面の鉛直開口部総面積 | m² | ||
| 加重平均窓高さ | m | ||
| 区画全面積(壁・天井・床、開口部を含む) | m² | ||
| 開口係数(m^(1/2)) | 1 | Result |
例題
= 12 m² · = 2 m · = 300 m²
= 0.05657 1
Standard and source
- Standard
- EN 1991-1-2:2002
- Result
- in 1
Reference to clause and equation, no standard text. The description is written in our own words.