Fire compartment opening factor O (EN 1991-1-2)
Opening factor O of a fire compartment for parametric temperature-time curves according to EN 1991-1-2 Annex A Eq. (A.4): O = (Av · √(heq / m)) / At.
- EN 1991-1-2:2002
Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.
Formula and quantities
| Symbol | Name | Unit | Note |
|---|---|---|---|
| Total area of vertical openings on all walls | m² | ||
| Weighted average window height | m | ||
| Total area of enclosure (walls, ceiling, floor including openings) | m² | ||
| Opening factor (in m^(1/2)) | 1 | Result |
Worked example
= 12 m² · = 2 m · = 300 m²
= 0.05657 1
Standard and source
- Standard
- EN 1991-1-2:2002
- Result
- in 1
Reference to clause and equation, no standard text. The description is written in our own words.