Verify a masonry wall to EC 6 with the simplified method

Describe the wall, the floor above it, the masonry unit and mortar, and the vertical loads. Mia first checks the application conditions of DIN EN 1996-3/NA, then verifies the vertical load capacity at the wall head, mid-height and foot and names the governing point.

Mia

Mia guides you step by stepShe guides you through the inputs and explains the results.

Worked example

KS 12 exterior wall · t = 175 mm · h = 2.70 m · lf = 6.00 m

Vertical load capacity verified, the wall foot governs
KS 12 exterior wall · t = 175 mm · h = 2.70 m · l_f = 6.00 m
Wall
Exterior wall, single-leaf, two-sided support
Masonry
KS 12 with NM IIa, fk = 6.0 N/mm²
Geometry
t = 175 mm, h = 2.70 m, a = t
Floor
End support, lf = 6.00 m, qk = 3.25 kN/m²
Loads at the wall head
NGk = 116.8 kN/m, NQk = 33.6 kN/m

Verify with the simplified method of DIN EN 1996-3/NA: single-leaf exterior wall of calcium silicate solid units KS 12 with NM IIa, t = 175 mm, long wall (1.00 m strip), two-sided support, standard overlap, RC floor fully supported (a = 175 mm), end support of a one-way intermediate floor with span 6.00 m, no centring strip, clear height 2.70 m, building height 18.6 m, qk = 3.25 kN/m² incl. partitions, characteristic loads at the wall head without self-weight NGk = 116.8 kN/m and NQk = 33.6 kN/m, unit weight 18 kN/m³.

Key results

Design load at the wall foot NEd
219.6 kN/m
Resistance at head and foot NRd (Φ₁ = 0.600)
357.0 kN/m
Resistance at mid-height NRd (Φ₂ = 0.703)
418.1 kN/m
Governing utilisation
η = 0.615 (wall foot)

fd = 0.85 · 6.0 / 1.5 = 3.40 N/mm²; ρ₂ = 0.75, hef = 2.025 m; NEd = 1.35 · 116.8 + 1.5 · 33.6 = 208.1 kN/m at the head plus the self-weight. The values match exercise 1.2 of Hochschule Karlsruhe (rounded there to 357/417/357 kN/m).

  • — One unit across the wall thickness (Einsteinmauerwerk).
  • — All application conditions of Table NA.2 are fulfilled (h = 2.70 m ≤ 2.75 m).
  • — The minimum load of 4.2.1.2 is not calculated, because wk is not given.

Required inputs

  • Wall type, lateral support and planned overlap
  • Wall thickness t, wall length l and clear storey height h
  • Floor support depth a, floor span lf, floor support and centring strip
  • Imposed floor load qk and building height above ground
  • Masonry unit and mortar, or fk from an approval
  • Characteristic loads NGk and NQk (or NEd) and whether they include the self-weight

What you receive

  • Table of all application conditions with required and actual values
  • fk with its table and row, fd, Φ₁ and Φ₂ with the effective height
  • NEd and NRd at the wall head, mid-height and foot with the utilisation
  • Minimum load check for wind-loaded end supports
  • Assumptions and normative references

Start from an input template

These templates prefill the form with typical inputs. They are not calculated results; the calculation runs in CALC.

Prepare your calculation
Dlubal CALC
Configure your masonry wall
Structural calculation to standard

System sketch

m
m
m
m
m
All required fields completed

Inputs completeReady to calculate

What this skill checks

Application conditions first

Building height, floor span, imposed load, support depth, wall thickness and clear height are checked against Table NA.2 before any load is asked; a violated condition is named with its value and limit.

Characteristic compressive strength f_k

f_k from Tables NA.D.1 to NA.D.10 for clay, calcium silicate, AAC, lightweight and normal concrete units with normal, thin-bed or lightweight mortar, or the value of an approval.

Floor rotation Φ₁ and slenderness Φ₂

Φ₁ for end supports, roof slabs, two-way slabs and centring strips to DIN EN 1996-3/NA:2019-12 with the factor a/t, Φ₂ at mid-height with the effective height of two-, three- or four-sided walls.

Self-weight and piers

The wall self-weight is added at mid-height and foot when the loads act at the wall head; walls and piers with A < 0.1 m² get the reduction factor 0.8 on f_d.

Minimum load of wind-loaded walls

For exterior walls that are end supports of floors, the minimum load of 4.2.1.2 is checked when w_k and the permanent load at the wall head are given.

Ready for your first check?

Start with the example and adapt it to your structural system.