Reduced concrete width by 500°C isotherm method (EN 1992-1-2)

  • Type: Property
  • Version 1
  • reviewed on 11/21/2026

Reduced effective width bfi of a concrete beam or column exposed to fire on both sides according to the 500°C isotherm method in EN 1992-1-2 Annex B.1: bfi = b - 2 · a500.

bfi=b−2⋅a500\displaystyle b_{fi} = b - 2 \cdot a_{500}
Apply in CALC

Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.

bfi

Formula and quantities

SymbolNameUnitNote
b\displaystyle bOriginal cross-section widthmm
a500\displaystyle a_{500}Depth of 500°C isotherm from fire-exposed sidemm
bfi\displaystyle b_{fi}Reduced effective concrete width in firemmResult

Worked example

b\displaystyle b = 300 mm · a500\displaystyle a_{500} = 30 mm

bfi\displaystyle b_{fi} = 240 mm

Standard and source

Result
bfi\displaystyle b_{fi} in mm

Reference to clause and equation, no standard text. The description is written in our own words.

Try it

Unit system
bfi\displaystyle b_{fi} = 240 mm= (300 mm) - 2 · (30 mm)