Design · Concrete

Fire design axial resistance of RC column (EN 1992-1-2)

  • Type: Resistance
  • Version 1
  • reviewed on 11/21/2026

Design axial compressive resistance of a reinforced concrete column in fire using the reduced concrete section according to EN 1992-1-2 Annex B.1: NRdfi = Acfi · fcdfi + As · fsdfi.

NRd,fi=Ac,fi⋅fcd,fi+As⋅fsd,fi\displaystyle N_{\mathrm{Rd},fi} = A_{\mathrm{c},fi} \cdot f_{cd,fi} + A_{s} \cdot f_{sd,fi}
Apply in CALC

Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.

AsNRdfi

Formula and quantities

SymbolNameUnitNote
Acfi\displaystyle A_{cfi}Reduced effective concrete cross-section areamm²
fcdfi\displaystyle f_{cdfi}Design compressive strength of concrete in fireN/m²
As\displaystyle A_{s}Total area of longitudinal reinforcementmm²
fsdfi\displaystyle f_{sdfi}Design yield strength of reinforcement in fireN/m²
NRdfi\displaystyle N_{Rdfi}Design axial resistance in firekNResult

Worked example

Acfi\displaystyle A_{cfi} = 100,000 mm² · fcdfi\displaystyle f_{cdfi} = 30,000,000 N/m² · As\displaystyle A_{s} = 2,400 mm² · fsdfi\displaystyle f_{sdfi} = 300,000,000 N/m²

NRdfi\displaystyle N_{Rdfi} = 3,720 kN

Standard and source

Result
NRdfi\displaystyle N_{Rdfi} in kN

Reference to clause and equation, no standard text. The description is written in our own words.

Try it

Unit system
NRdfi\displaystyle N_{Rdfi} = 3,720 kN= (100,000 mm²) · (30,000,000 N/m²) + (2,400 mm²) · (300,000,000 N/m²)

Continue with Mia

Fills the input field in CALC; nothing is sent until you send it.

No matching formula yet? Find the right calculation rule.

Describe what you want to determine. Mia searches the formula catalog first and clarifies assumptions before anything is calculated.

The search starts in Design › Concrete.

Miaknows the formula catalog and asks for what is missing.

You clarify missing information with Mia in the next step. Nothing is calculated yet.