Fire design axial compression resistance of timber column (EN 1995-1-2)
Design axial compression resistance of a timber column in fire including buckling reduction factor according to EN 1995-1-2 Clause 4.2.2: NcRdfi = kcfi · Aef · fc0dfi.
- EN 1995-1-2:2004
Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.
Formula and quantities
| Symbol | Name | Unit | Note |
|---|---|---|---|
| Buckling reduction factor for residual section in fire | 1 | ||
| Effective residual cross-sectional area | mm² | ||
| Design compressive strength parallel to grain in fire | N/m² | ||
| Design axial compression resistance in fire | kN | Result |
Worked example
= 0.65 1 · = 20,164 mm² · = 27,600,000 N/m²
= 361.74 kN
Standard and source
- Standard
- EN 1995-1-2:2004
- Result
- in kN
Reference to clause and equation, no standard text. The description is written in our own words.