Design · Concrete

Effective height factor lambda for compression zone

  • Type: Coefficient
  • Version 1
  • reviewed on 11/9/2026

Factor lambda defining the effective depth of the rectangular compression zone when fck > 50 MPa: λ = 0.8 - (fck - 50 MPa) / (400 MPa).

λ=0.8−(fck−50)/400\displaystyle \lambda = 0.8 - (f_{ck} - 50) / 400
Apply in CALC

Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.

fck

Formula and quantities

SymbolNameUnitNote
fck\displaystyle f_{ck}Characteristic compressive strengthN/mm²
λ\displaystyle \lambdaEffective compression zone factor–Result

Worked example

fck\displaystyle f_{ck} = 70 N/mm²

λ\displaystyle \lambda = 0.75 · Source: EN 1992-1-1:2004 Eq. (3.19)

Scope and standard

High-strength concrete with 50 MPa < f_ck <= 90 MPa (for f_ck <= 50 MPa, lambda = 0.8).

Standard
EN 1992-1-1:2004, clause 3.1.7 (3), Eq. (3.19)
Result
λ\displaystyle \lambda (dimensionless)

Reference to clause and equation, no standard text. The description is written in our own words.

Try it

Unit system
λ\displaystyle \lambda = 0.75= 0.8 - ((70 N/mm²) - 50 [N/mm²]) / (400 [N/mm²])